High Voltage Outdoor Station Post Ceramic Insulator | ||||||
ANSI Class | TR205 | TR208 | TR210 | TR214 | TR216 | |
Dimensions | ||||||
Diameter | mm | 178 | 178 | 191 | 203 | 232 |
Height | mm | 254 | 356 | 457 | 559 | 762 |
Creepage distance | mm | 394 | 610 | 940 | 1092 | 1892 |
Mechanical Values | ||||||
Torsion Strength | kn | 38 | 44.5 | 53 | 62 | 71 |
Compression Strength | kn | 44.5 | 44.5 | 66.7 | 66.7 | 111 |
Cantilever Strength | kn | 8.9 | 8.9 | 8.9 | 8.9 | 6.7 |
Electrical Values | ||||||
power frequency dry withstand voltage | kv | 85 | 110 | 145 | 170 | 235 |
power frequency wet withstand voltage | kv | 55 | 75 | 100 | 125 | 180 |
Critical impulse flashover voltage,positive | kv | 125 | 170 | 225 | 280 | 390 |
Critical impulse flashover voltage,negative | kv | 200 | 250 | 290 | 340 | 475 |
Impulse Withstand voltage | kv | 110 | 150 | 200 | 250 | 300 |
Power frequency dry flashover voltage | kv | 55 | 75 | 100 | 125 | 180 |
Power frequency wet flashover voltage | kv | 40 | 60 | 80 | 100 | 145 |
Radio influence Voltage Data | ||||||
Impulse Withstand Voltage | kv | 110 | 150 | 200 | 250 | 350 |
Net weight,approximate | kg | 7 | 11 | 16 | 21 | 30 |